Owner's Manual

Electronic Air Purification System

Smoke Eliminator SE 400 and SE 800

Design  |  Installation  |  Servicing  |  Reference

 

End Page 1 of Paper Manual


 
Contents

Page Numbers Coincide with the Paper Manual


Section I Design

Page
1. Introduction ...................................................................... 3
2.  The Filter System ...................................................................... 3
3.  Specifications ...................................................................... 4

Section II Installation
   
1. Installation ...................................................................... 5-6
2.  Diagrams ...................................................................... 7

Section III Servicing and Maintenance
 
1.  Servicing / Maintenance ...................................................................... 8
2.  Parts List ...................................................................... 9
3.  Exploded Views ...................................................................... 10

Section IV Reference
 
1.  Wiring Diagram SE400 ...................................................................... 11
2.  Wiring Diagram SE800 ...................................................................... 12
     

This manual provides information for installation, operation and maintenance of
your Trion SE400E & SE800E. Before installing and using the air purifier, carefully
read these instructions to ensure maximum benefits from the unit, and to avoid
needless service costs that may result from improper installation
and maintenance.

Return to Top

End Page 2 of Paper Manual


Eliminator SE400E & SE800E

Section I Design

1. Introduction

The Trion Eliminator SE400E & SE800E are commercial air purifiers that have been specifically designed to remove airborne pollutants - including tobacco smoke, dust, pollen and mold spores - in rooms and areas where people work or relax. They are designed to be mounted onto a solid ceiling, semi-recessed for into a suspended ceiling, or wall mounted (SE400E only). Where appropriate they can also draw in additional fresh air.

Their features make them the ideal air purifier for installations into areas such as offices, conference rooms, restaurants, designated smoking areas, institutions and waiting rooms or any other place where people gather.

HOW THEY WORK

The Trion SE400E & SE800E utilize the principle of Electrostatic Precipitation. Air is drawn into the intake, through the metal prefilter, which traps lint and large dust particles. The remaining particles, some as small as 0.01 microns*, pass into a strong electrical field (ionizing section) where the particles receive an electrical charge. The charged particles pass onto a series of equally spaced parallel plates (collector section). Each alternate plate is charged with the same polarity as the particles, which are repelled, while the interleaving plates are grounded, and therefore attract and collect the particles. * The diameter of a human hair is about 100 micron!

2. The Filter System

There are two filters in your air cleaner - THE PRE-FILTER: This is the mechanical filter that lies behind the inlet grill. It is designed to remove large particles and can be washed many times before replacement.

THE ELECTROSTATIC FILTER: This is the deep aluminum assembly (Collector Cell) located immediately behind the pre-filter and is the heart of your air cleaner. It uses an electrostatic charge to remove particles so small that it would take a pile of many millions to cover a pinhead. When dirty it can be washed and reused indefinitely.

FILTER REMOVAL

TRION SE400E
Turn the control switch off before removing cell. Press the two cell access latches and the hinged door will swing down. Remove pre-filter by turning pre-filter clip 90 degrees (fig 2). While supporting the weight of the Collector Cell, loosen the filter retaining screw (fig 3). The filter retaining plate will now open allowing the filter to be removed (fig 4). To reinstall the filter, simply reverse above procedure.

TRION SE800E
The two hinged access doors are secured with retaining screws (fig 3). Release screws to allow the doors to swing down. Remove the Collector Cells as described above.

INSTALLATION LOCATION

The most effective location for the air purifier is
the center of the area to be cleaned because
the dirty air is pulled into the center of the unit
and discharged equally out the four sides. If
more than one unit is required, space them
evenly over the area to be cleaned.

Return to Top

End Page 3 of Paper Manual


3. Specifications
 
Model SE400E SE800E
Dimensions Depth: 9.5" Depth: 9.5"
  Width: 22.5" Width: 22.5"
  Length: 22.5" Length: 46.12"

Installation

Surface mounted, recessed into suspended ceiling, or wall (SE400 only) mounted.
Weight 42 lbs. / shipping 48 lbs. 80 lbs. / shipping 86 lbs.
Input Power 120 Volts, 1 Phase, 60 Hz 120 Volts, 1 Phase, 60 Hz
Power Consumed 1.8 Amps, 155 Watts 3.4 Amps, 270 Watts
Controls Hard-wired remote Control with 3 speed selector switch with air-dry (fan only) facility Hard-wired remote Control with 3 speed selector switch with air-dry (fan only) facility
Motor 1/20 HP, 3-speed, Ball Bearing (2) 1/20 HP, 3-speed, Ball Bearing
Air Flow 200, 300, 400 CFM 400, 600, 800 CFM
Sound Rating 38, 55, 62 dBa 41, 58, 65 dBa
Safety Feature Interlock to cell access door Interlock to cell access door
Features Anti-arc circuitry
Power to cell indicator
Fresh air inlet
Dry (fan only) cycle
Anti-arc circuitry
Power to cell indicator
Fresh air inlet
Dry (fan only) cycle
Options Fresh air damper system Fresh air damper system

Return to Top

End Page 4 of Paper Manual


Eliminator SE400E & SE800E

Section II Installation

1. Installation

CAUTION:
ELECTRONIC AIR CLEANERS CANNOT BE USED IN AREAS WHERE COMBUSTIBLE GASES OR VAPORS ARE PRESENT.

MECHANICAL
The unit has been designed so that it can fit either surface mounted onto the ceiling, semi-recessed into a T-Bar suspended ceiling or wall mounted (SE400E only). When installed with a T-Bar suspended ceiling NEVER support the unit from the TBars, the unit must be supported from the permanent ceiling.

SUSPENDED CEILING INSTALLATION
To hang the unit into a suspended ceiling, proceed as follows:

  1. Unpack the unit, open filter access door and remove prefilter and cell (see filter removal in section 2).
  2. Install -20 eyebolts into mounting slots with large diameter washers and lock-nuts as shown in sketch A. Alternatively, use drop rods.
  3. Install trim as shown in sketch A.
  4. Select and remove a ceiling tile near the center of the area to be cleaned by the unit.
  5. Attach a length of safety chain to each of the four eyebolts or fit threaded rod. Fasten securely.
  6. Lift unit into place and support unit while securing to permanent ceiling, ceiling joists, etc. See sketch A.
     
    CAUTION:
    IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE ADEQUATE MOUNTING COMPONENTS ARE USED.

    DO NOT ALLOW WEIGHT OF UNIT TO REST ON SUSPENDED CEILING SUPPORT RAILS.


  7. Make electrical connections as detailed in next
    section.
  8. Re-install cell and prefilter.
  9. Close access door and unit is ready for
    operation.

SOLID CEILING MOUNTING
To mount the unit to a solid ceiling, proceed as follows:

  1. Unpack the unit, open filter access door and remove prefilter and cell (see filter removal in section 2).
  2. Select a location near the center of the area to be cleaned. lf you are fitting to wooden ceiling joists, locate the position of joists.
  3. Using the template provided, drill four holes into the ceiling and fit four 5/16 lag screws in the joists. Hex-headed screws will give easier access for final tightening. Do not tighten fully home.
  4. Lift the unit to where the large end of the keyhole slots in the top of the cabinet fit over the screw heads. Slide the unit so that the narrow ends of the mounting slots are located under the screw heads. Tighten the screws fully home.
  5. Install the lockdown location screw as shown on template.
  6. Make electrical connections as detailed in next section.
  7. Re-install cell and pre-filter.
  8. Close access door and unit is ready for operation.

WALL MOUNTED (SE400E Only)
Filter removal will be simpler if the unit is positioned with the access door hinge in a vertical plane. Locate the wall studs and follow the mounting instructions for SOLID CEILING MOUNTING.
 

ELECTRICAL: WARNING:
THIS APPLIANCE MUST BE ELECTRICALLY GROUNDED.

 

NOTE: This unit is designed to be permanently connected to fixed wiring. Installation must comply with all applicable electrical codes.

Return to Top

End Page 5 of Paper Manual


Hard wired remote control
Two sets of wiring are required to connect the unit. Main power to the unit is 120V, 60Hz, 1Ph, rated 5 Amp - Live, Neutral and Ground. A 5-conductor 5 Amp rated cable is required from the unit to remote control. Run the 5-conductor cable and the main power connection through the cable entry knockouts (see Fig. 5) in the cabinet and connect to the input terminal block (Fig. 6) as shown in the wiring diagram on page 10 and 11. Mount the remote control in the desired position and connect the 5-conductor cable leads to the numbered terminals as shown in the wiring diagram.

Return to Top

End Page 6 of Paper Manual


2. Diagrams
 

Figure 1

 
Figure 2

 
Figure 3

 
Figure 4

 
Figure 5

 
Figure 6

 

Return to Top

End Page 7 of Paper Manual


Eliminator SE400E & SE800E

Section III Service and Maintenance

1. Servicing and Maintenance

Beyond an occasional wipe down with a damp cloth, the units need little in the way of maintenance.

However, the units are designed to collect airborne dirt and from time to time will require routine servicing to remove the accumulation.

The service interval varies considerably between applications, but typically will range from six weeks in a busy bar up to several months in a quiet office.

During normal operation, the unit will make an occasional snapping noise. This is caused by large pieces of dirt accumulating on the electronic filter and is not dangerous. The Trion SE400E & SE800E units have anti-arcing circuitry to eliminate the nuisance of constant arcing. If, however, the arcing occurs every minute or two, it is an indication that the unit needs cleaning.

When a service is due proceed as follows:

  1. Remove pre-filter and either vacuum clean it or wash as described below.
  2. To clean the electronic filter, soak it in a hot (not boiling), a strong non-caustic detergent solution cleaner. Trion can supply an excellent detergent- TriDex obtainable through your Dealer. Alternatively, a dishwasher detergent does an excellent job. Soak the collector cell for several hours, then rinse with clean water. Do not physically try to rub the dirt off since this can cause damage to the filter.
  3. Allow the filter to dry thoroughly - preferably overnight- and replace into the unit or alternatively use force air dry setting on the unit.

Trion has a policy of continuous product improvement, and reserves the right to make changes in design and specification without notice.

Return to Top

End Page 8 of Paper Manual


2. Parts List
 

Item Part Number Description Qty/Unit SE 400E Qty/Unit SE800E
1 454027-001 Cabinet Assembly, SE400E 1 -
2 454028-001 Cabinet Assembly, SE800E - 1
3 453844-003 Cell Access Cover 1 -
4 453845-001 Discharge Cover 1 2
5 453845-001 Cell Access Cover - 2
6 153853-001 Hinge Pin 2 4
7 453855-001 Grill 4 6
8 453856-001 Corner 4 4
9 453857-001 Grill Filler - 2
10 253863-001 Pre-filter 1 2
11 441730-103 Collector Cell 1 2
12 150685-001 Cell Retaining Clip 1 2
13 353842-001 Cell Latch 1 2
14 153854-001 Thumb Screw 1 2
15 244225-002 Bolt Retainer 1 6
16 345109-001 Cell Contact Assembly 1 2
17 453840-001 Cell Contact Support 1 -
18 453841-001 Cell Contact Support - 1
19 242404-00 Interlock Switch 2 4
20 147214-001 Insulator 2 4
21 350950-003 Power Supply Assembly 1 1
22 254167-003 Step-down Transformer 120V/24V 1 -
23 254167-004 Step-down Transformer 120V/24V - 1
24 453847-001 Motor Mounting Bracket 1 2
25 254026-002 Motor, 120V/60Hz 1 2
26 142153-001 Ground Contact 1 2
27 254101-001 Fan 1 2
28 453858-001 Inlet Ring 1 2
29 EST-1124 Terminal Block 1 14
30 253850-001 Terminal Block Cover 1 1
31 253851-001 Duct Cover Plate 1 2
32 153848-001 Interlock Switch Actuator 1 -
33 153849-001 Interlock Switch Actuator - 2
34 253852-001 Access Cover Latch 2 -
35 120035-210 Flat Head Screw - 4
36 234711-002 Retaining Nut - 4
37 354267-001 Remote Control Assembly 1 1
37a 250056-001 Rotary Switch 1 1
37b 242235-001 Switch Knob 1 1

Return to Top

End Page 9 of Paper Manual


3. Exploded Views
 


Click to Activate Controls

Free Report - Mini-Course
Confessions From The World's Most Successful Commercial Air Cleaner Salesman.

Name:

Email:


Don't worry, we never sell, rent or share your email.

Over 6,000 Satisfied Customers!

SE400E


SE800E

Return to Top

End Page 10 of Paper Manual


Eliminator SE400E & SE800E

Section IV Reference

1. Wiring Diagram SE 400 E

Return to Top

End Page 11 of Paper Manual


 

2. Wiring Diagram SE 400 E


Manual Part Number 154385-002, June 2001

Return to Top

End Page 12 of Paper Manual


Page copy protected against web site content infringement by Copyscape

Supplemental Navigation


Home >
Air Cleaner, Air Purifier, Smoke Eater, Commercial Air Cleaner, Commercial Air Purifier, Commercial Smoke Eater,
Filterless Air Purifier

Buyer's Guide >

Air Cleaner Details > Air Cleaners, Air Purifiers, Smoke Eaters, Commercial Air Cleaners, Commercial Air Purifiers, Commercial Smoke Eaters

Placement > Electrostatic Air Cleaner, Electrostatic Air Purifier

Installation > Electrostatic Air Cleaners, Electrostatic Air Purifiers

Rave Reviews >
Trion Electronic Air Cleaner, Electronic Air Cleaner, Electronic Air Purifier, Air Cleaner Electronic

FAQs >
Smoke Air Purifier, Smoke Air Cleaner

Satisfaction Guarantee >
Electronic Air Cleaners, Electronic Air Purifiers

Buy Now >
Commercial Air Purification Systems, Commercial Air Filtration, Commercial Air Purification